K-LB-2.30G
型號:
K-LB-2.30G
Number of protected signal lines | 4 | |
---|---|---|
Topology | grounded | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Electrical specifications | ||
Connection | protected area: terminals 5, 6; 7, 8 unprotected area: terminals 1, 2; 3, 4 | |
Rated current | 250 mA | |
Leakage current | < 10 μA at 24 V and 25 °C (77 °F) , line-line | |
Nominal voltage | 24 V DC | |
Maximum continuous operating voltage | 30 V DC | |
Series resistance | < 0.5 Ω per line | |
Impulse rating | 10 kV/5 kA (category C2) 2 kV/2 kA (category D1) | |
Impulse discharge current (10/350 μs) | 2 kA per line (2x) | |
Nominal discharge current (8/20 μs) | 5 kA per line (10x) | |
Rated surge current (8/20 μs) | 10 kA per line (1x) | |
Total discharge current (8/20 μs) | 20 kA (1x) | |
Voltage protection level | max. 100 V line-line for nominal discharge current In max. 50 V line-earth for nominal discharge current In | |
Impulse reset time | < 30 ms | |
Insertion loss | ≤ 0.05 dB, at 0 ... 4 kHz, in 600 Ω-System ≤ 3 dB, at 0 ... 174 kHz, in 100 Ω-System | |
Indicators/settings | ||
Labeling | space for labeling at the front | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Surge protective devices for low voltage | EN 61643-21:2001+A1:2009+A2:2013 IEC 61643-21:2001+A1:2008+A2:2012 | |
Operating conditions | ||
Installation conditions | ||
Mounting location | indoor | |
Ambient conditions | ||
Ambient temperature | -30 ... 80 °C (-22 ... 176 °F) For usage in hazardous area observe EC-type examination certificate. | |
Relative humidity | 5 ... 95 % | |
Mechanical specifications |