KFD2-CD-EX1.32安全柵
型號:
KFD2-CD-EX1.32
Signal type | Analog output | |
---|---|---|
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 7+, 8- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Rated current | current output: ≤ 50 mA ; voltage output: ≤ 20 mA | |
Power dissipation | 1.2 W | |
Input | ||
Connection side | control side | |
Connection | terminals 9+, 10-, 11+ | |
Voltage drop | optional current input: approx. 4 V at 20 mA | |
Input current | ≤ 100 μA up to 50 °C (122 °F) at 10 V | |
Limit | optional current input: Input current: approx. ≤40 mA optional voltage input: input voltage: 12 V DC | |
Transmission range | optional current input: 0 ... 20 mA/optional voltage input: 0 ... 10 V | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Voltage | optional current output: 17 V at 20 mA/optional voltage output: 0 ... 10 V | |
Current | optional current output: 0 ... 20 mA/optional voltage output: ≤ 20 mA | |
Load | optional current output: max. 850 Ω optional voltage output: output resistance max. 3 Ω | |
Transfer characteristics | ||
Accuracy | 0.1 % | |
Deviation | ||
After calibration | ≤ ± 0.1 % incl. non-linearity and hysteresis at 20 °C (68 °F) | |
Influence of ambient temperature | ≤ ± 0.01 %/K | |
Rise time | < 10 ms |