HICTB16-YC3-RRB-KS-CC-AI16 現(xiàn)貨直發(fā)

型號: HICTB16-YC3-RRB-KS-CC-AI16

--- 產(chǎn)品參數(shù) ---

  • HICTB16-YC 1

--- 產(chǎn)品詳情 ---

參數(shù)表節(jié)選:的技術(shù)參數(shù)  HiCTB16-YC3-RRB-KS-CC-AI16

Supply
ConnectionX20: terminals 3, 5(+); 4, 6(-)
Nominal voltage24 V DC , in consideration of rated voltage of used isolators
Voltage drop0.9 V , voltage drop across the series diode on the termination board must be considered
Ripple≤ 10 %
Fusing4 A , in each case for 16 modules
Power dissipation≤ 500 mW , without modules
Reverse polarity protectionyes
Redundancy
SupplyRedundancy available. The supply for the isolators is decoupled, monitored and fused.
Fault indication output
ConnectionX20: terminals 1, 2
Output typevolt-free contact
Switch behaviourno fault: relay contact closed
power supply fault: relay contact open
module fault: relay contact open
Contact loading30 V DC , 1 A
Indicators/settings
Display elementsLEDs PWR ON (Termination Board power supply)
- LED power supply I, green LED
- LED power supply II, green LED
LED FAULT (fault indication), red LED
- LED lits: module fault
- LED flashes: power supply fault
Directive conformity
Electromagnetic compatibility 
 Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connection 
 Field sideexplosion hazardous area: spring terminals , blue
 Control sidenon-explosion hazardous area: Yokogawa system connector, 40-pin
 Supplypluggable screw terminals , black
 Fault outputpluggable screw terminals , black
Core cross sectionspring terminals:
rigid: 0.2 ... 2.5 mm2
flexible: 0.25 ... 1.5 mm2
Materialhousing: polycarbonate
Massapprox. 645 g
Dimensions240 x 175 x 153 mm (9.45 x 6.9 x 6.02 inch) (W x H x D) , depth including module assembly
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateCESI 06 ATEX 022
 Marking
Ex-Hexagon

II (1)G [Ex ia Ga] IIC
 

Ex-Hexagon

II (1)D [Ex ia Da] IIIC
 

Ex-Hexagon

I (M1) [Ex ia Ma] I

Non-hazardous area 
 Maximum safe voltage250 V (Attention! Um is no rated voltage.)
Galvanic isolation 
 Field circuit/control circuitsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity 
 Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 50303:2000