FI-PFH-NS0137-R 現貨直發
型號:
FI-PFH-NS0137-R
HART signal channels (non-intrinsically safe) | ||
---|---|---|
Load resistor | 220 Ω , switchable on | |
Interface | ||
Type | multiplexer connection : IDC plug, 26-pin | |
Signal lines | ||
Rated current | max. 30 mA per channel | |
Indicators/settings | ||
Control elements | DIP switch | |
DIP switch | selection of operating mode: - ON: without load resistor - OFF: with load resistor | |
Factory setting | DIP switches S1 and S2: ON | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2017 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | 0 ... 50 °C (32 ... 122 °F) | |
Storage temperature | -15 ... 50 °C (5 ... 122 °F) | |
Relative humidity | ≤ 93 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | ||
Field side | screw terminals , green | |
Control side | screw terminals , green HART : 1 x IDC plug, 26-pin | |
Core cross section | 0.25 ... 1.5 mm2 (24 ... 16 AWG) | |
Material | ||
Housing | PVC | |
Mass | approx. 210 g | |
Dimensions | 110 x 125 x 61 mm (4.3 x 4.9 x 2.4 inch) (W x H x D) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 11 CERT 1930 X | |
Marking | II 3G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-15:2010 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |