KFD0-CS-EX2.51P 倍加福 現(xiàn)貨直發(fā)
型號:
KFD0-CS-EX2.51P
General specifications | ||
---|---|---|
Signal type | Analog input/analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Systematic capability (SC) | SC 3 | |
Supply | ||
Rated voltage | loop powered | |
Control circuit | ||
Connection | terminals 12-, 11+; 8-, 10-, 9+ | |
Voltage | 4 ... 35 V DC | |
Current | 0 ... 40 mA | |
Power dissipation | at 40 mA and Uin < 22 V: 700 mW per channel at 40 mA and Uin > 22 V: 1.2 W per channel | |
Field circuit | ||
Connection | terminals 1+, 2-; 4+, 5- | |
Voltage | for 4 V < Uin < 24 V: ≥ Uin - (0.37 x current in mA) - 1.0 for Uin > 24 V: ≥ 21 V - (0.36 x current in mA) | |
Short-circuit current | at Uin > 24 V: ≤ 65 mA | |
Transfer current | ≤ 40 mA | |
Transfer characteristics | ||
Accuracy | 1 % | |
Deviation | ||
After calibration | ≤ ± 200 μA; incl. calibration, linearity, hysteresis and load fluctuations at the field side up to a load of 1 kΩ and current ≤ 20 mA at 20 °C (68 °F) | |
Influence of ambient temperature | ≤ ± 2 μA/K at Uin ≤ 20 V; ≤ ± 5 μA/K at Uin > 20 V | |
Rise time | ≤ 5 ms at bounce from 4 ... 20 mA and Uin < 24 V | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Indicators/settings | ||
Labeling | space for labeling at the front |